ZnPS LV Power Capacitor
You have purchased the ZnPS Cylindrical Type Power Capacitor, which is produced by Kondaş Capacitors under the standards of TS EN 60831 & IEC 60831. For maximum benefit and safety, please follow the instructions listed below.
WARNING: After operation, please wait for 5 mins, perfırn a short circuit and earth the capacitor after disconnection from the energy source.
Maximum power applied on bolt nut when mounting the capacitor shall be no more than 1 kg.m
Avoid using the product in extremely hot environments
Use conductive material that are compatible with terminals (which are listed below) when connecting capacitor units.
Earthing of the capacitor shall be made through using the mounting screw on the bottom lid.
Conductives should be connected with the screws on terminals with an applied power of 0.3 kg.m, and shall be regularly checked in order to avoid a loosening up. (Loose connection on terminals cause overheating and therefore defects in time)
Select the PFC contactors in relation to the AC2-AC3 rated voltage (not Ith)
On automatic compensation; the contactors that command the first step group capacitors should be selected 1.5 times the rated voltage of the capacitor. For the remaining steps, the multiplier is 1.25
The fuses on the feeder should be selected 1.7 times the rated voltage of the capacitor
Feeding panel or other circuit breakers should be selected 1.3 times the rated voltage of the capacitor
Environment that the capacitors work in should be dry at all times and ventilated regularly
On automatic compensation, select the group capacitors in accordance to the need of the system
The current transformer that will be connected to the reactive power control relay should be selected in accordance to the sort of premise that is intended to be compensated.
The current transformer should be connected before the capacitors and should be located at the primary entrance of the building.
The ratio of the current transformer and the intended cos Q should be typed inside the reactive power control relay. Other necessary settings should be altered in relation to the instructions of the relay.
The capacitor is provided with a discharge resistor. Do not rip it off.
In order to allow the overpressure disconnectors to operate appropriately, there should be at least 30mm’s of distance above the terminals after mounting the capacitor.
Thanks for selecting Kondaş products.